������������������������ SECTION 15311
����������� RETROFIT-SPRINKLER PIPING COVER SYSTEM
PART 1� GENERAL
1.1 SECTION INCLUDES
��� A.� Modular piping cover system for installation of metal piping system in existing construction.
��� B.� Modular combination pipe hanger and cover system for installation of CPVC piping system in existing construction.
1.2 RELATED SECTIONS
��� A.� Section 15310 - Fire Protection Piping.
1.3 REFERENCES
��� A.� ASTM E 84 - Standard Test Method for Surface Burning Characteristics of Building Materials.
��� B.� NFPA 13 - Installation of Sprinkler Systems.
��� C.� "Building Materials Directory"; Underwriters Laboratories Inc.
��� D.� "Fire Protection Equipment Directory"; Underwriters Laboratories Inc.
1.4 SUBMITTALS
��� A.� Submit under provisions of Section 01300.
��� B.� Product Data:� Include manufacturer's installation instructions.
��� C.� Certification of UL listings.
1.5 DELIVERY, STORAGE, AND HANDLING
��� A.� Store materials in areas where temperature will be maintained above 35 degrees F.
��� B.� Protect from exposure to direct sunlight.
��� C.� Stack or store in such a manner to prevent distortion of shape.
1.6 WARRANTY
��� A.� Provide manufacturer's 10 year material warranty.
PART 2� PRODUCTS
2.1 MANUFACTURERS
��� A.� Provide "DecoShield" piping cover system manufactured by Creative Systems, Inc., One Parker Place, P.O. Box 957, Janesville, WI 53547.� Telephone: (608) 757-0717.� Fax: (608) 757-0721.
2.2 MATERIALS
��� A.� Piping Cover System:� Modular, snap-fit cover units, clips, and anchors, which once assembled, render the cover essentially irremovable with the use of ordinary tools; UL listed for use with CPVC piping systems.
��� B.� Cover Units:� L-shaped and U-shaped cross-section units of flame retardant resin material, paintable finish.
������� 1.� Resin:� B.F. Goodrich Co. "TempRite."
������� 2.� Surface burning characteristics when tested in accordance with ASTM E 84:
����������� a.� Flame spread:� 20.
����������� b.� Smoke developed:� 250.
������� 3.� Unit length:� 7.5 feet.
������� 4.� Provide coupling fittings for joining units end to end and prefabricated inside and outside corner fittings and end caps.
������� 5.� Provide sidewall sprinkler head housing accommodating NFPA 13 4-inch drop assembly requirements.
������� 6.� Provide mounting clips to secure covers to wall/ceiling.
��� C.� Pipe Hangers for CPVC Piping:� Manufactured by cover system manufacturer; UL listed; requiring no special tools for installation.
������� 1.� For supporting piping only:� "Snap-2" hangers.
������� 2.� For supporting both piping and covers:� "Combo" hangers that automatically position pipe in cover.
��� D.� Pipe Hangers for Copper and Steel Piping:� Design and dimensions compatible with cover system; UL listed.
��� E.� Paint:� Acrylic latex; color to match adjoining surfaces.
PART 3� EXECUTION
3.1 INSTALLATION
��� A.� Install in accordance with the manufacturer's instructions and recommendations.
��� B.� See Section 15310 - Fire Protection Piping for requirements for installation of piping.� Space hangers supporting piping in accordance with applicable requirements.
��� C.� Space hangers and mounting clips supporting covers to hold the covers and fittings firmly against the mounting surface without gaps or unpleasant appearance.
��� D.� Install cover units using coupling fittings and corner units as required.
��� E.� Paint entire cover assembly.� Cover sprinkler heads carefully during painting and remove covering completely immediately after painting.